MR380 1-3

MR380 1-3 Universal MM/SM E-Stop and Switch Controller

MR380 1-3 Universal MM/SM E-Stop and Switch Controller

MR380 Fiber Optic Signaling Sensors are used anywhere where conventional electromechanical controls cannot be used – both harsh and hazardous environments. The MR380-1-3 Universal Controller Module is the active optical and electrical interface for all MR380 series ZapFREE® Emergency Stop, Microswitch, and other Signaling Sensor products. This controller is compatible with both multimode (50/125 and 62.5/125) and single mode (9/125) based sensors in the MR380 series.

Specifications

Functional States Applies to MR380 E-STOP Sensor Only
Normal RESET (Up Position)

Digital 5V and 24V Outputs=HI

NC contacts=Closed, NO contacts=Open

ACTIVATED (Down Position)

Broken Fiber, Loss of Optical Signal, or Controller Failure

Digital 5V and 24V Outputs=LOW

NC contacts=Open, NO contacts=Closed

Digital Outputs
5V Logic 5 VDC/2k Ω Load Max
24V Logic 24 VDC/2k Ω Load Max
Relay Contacts 2x Form C (CO)
Switching Power Rating 60 W / 62.5 VA
Contact Material AgNi, Gold Covered
DC Rating 75 V @ 0.75A; 24 V @ 2A
AC Rating 50 V @ 1A; 24 V @ 2A
Optical Class I Eye Safe
MR380-1-3 Single Mode or Multimode, 1310nm, Class I Eye Safe, System Loss Budget=25dB
Maximum Distance Distance is a function of user’s system loss budget which is the total round-trip loss of all optical link components – sensor(s), connectors, splices and cable segments.
Consult Application Note AN118 for more information.
Interface NOTE: Electrical connections shall not exceed 3 meters.
Electrical 10-pin Screw Terminal, 30-14 AWG (Phoenix Mating Plug 1803659)
Optical LC-Duplex, 50/125 OM-2 or 62.5/125μm OM-1 Multimode Fiber
Power Supply +24 VDC, <80 mA input
Functional Safety Consult Declaration of Conformity for additional F.S. information
Classification MR380 System is classified Category 2 per ISO13849-1
MTTFd 4.14 E+06 hours (70.8 years)
Performance Level (PL) PL=c
Safety Integrity Level (SIL) SIL=1
Explosive Atmospheres
EX Classification Controller shall be installed in non-hazardous location only
Power supply to Controller shall be current limited to 200mA or less
IECEx Test Report (ExTR) GB/CML/ExTR 16.0105/00 (Multimode Controllers)
ATEX [EPL Mb/Gb/Gc/Db/Dc]
EAEU/GOST [EPL Mb/Gb/Gc/Db/Dc]
IEC Ex [EPL Mb/Gb/Gc/Db/Dc]
North America Controller shall be installed in non-hazardous location only
Environmental Performance
Temperature/Humidity -5°C to +55°C (23°F to +131°F), 0-95% RH, Non-Condensing
Ingress Protection IP50
Physical Attributes
Mounting 35mm DIN Rail
Housing 11.4 x 8.9 x 3.2 cm (4.5 x 3.5 x 1.25 inches)
Weight 230 g (8.1 oz)

Specifications subject to change without notice

 

Features

  • DIN rail mountable module
  • Ex rated Inherently Safe Optical Radiation
  • Controller is installed outside the hazardous area
  • Interference-free transmission up to 10km (6 miles) with single mode fiber
  • Universal controller supports both multimode (50/125 and 62.5/125) and single mode (9/125) fiber links
  • Depending on sensor type, multiple sensors can be optically wired in series

Interfaces

  • DPDT relay contacts
  • Digital status outputs, 5V and 24V
  • Depending on sensor type, digital outputs and relay implement know default failure state